021 8690 6777
0812 9049 9480
Home   »   Produk   »   HOBO   »   Energy & Power Sensors

Split-Core Bi-Polar DC Transducer Sensor - T-VER-971BP-200


Untuk memesan, silahkan tekan tombol ORDER. Anda bisa memesan barang secara Online.


Anda juga bisa memesan via telephone, silakan hubungi sales consultant. Hotline kami di (021) 8690 6777 sales Consultant kami akan menjelaskan detail produk dan harga terbaru. atau email ke alamat sales@alatperaga.com

Split-Core Bi-Polar DC Transducer

Split-Core Bi-Polar DC Transducer sensor that measures up to 200 Amps of DC current in both flow directions.

Requires analog port selection during U30 system configuration and use of a S-FS-CVIAwhen using the H22-001 data logger. When using a U12 data logger, this sensor requires a 4-20mA input cable (CABLE-4-20mA) and external power provided by an AC adapter (AC-SENS-1).

Note: For measurements larger than 120A the device must be powered by a minimum of 15V to maintain expected accuracy.

The T-VER-971BP-200 Sensor is for use inIndoor environments

The T-VER-971BP-200 Sensor supports the following measurements:
DC Current

Features :

  • Measures current flow in both directions which is especially beneficial for Solar PV applications.
  • Adjustable span range
  • Small size, split-core for ease of installation

Specifications :

DC Amperage (bi-polar)
Measurement range: +/- 2 to +/- 200 (via span adjust)
Accuracy (below 100A span): +/- .5 A
Accuracy (above 100A span): +/- .5% full scale
Sensor supply:  12 - 24 DC (15 VDC min. for cuurents > 120 A), 35 mA no-load to 110 mA at 200 A current
Isolation:  600 VAC rms
Operating temperature range:  -30 to 60C (-22 to 140F)
Humidity range:  10 - 90% non-condensing
Response time:  2 sec.
Output:  (bi-polar) 4 - 20mA
Dimensions: 3.1x2.8x1.4 in. (79x70x36 mm)
Weight:  5.25 oz.
Sensor opening:  1.1x.9 in. (28x23 mm)
LED indications:  single green blink=Norm, double green=Over Span, red+green=Over Limit, solid red=overload